T8000-R Series Wall Mount CO2 and Temperature Transmitters

Model:

T8000-R

Brand

Telaire - T8000-R Series Wall Mount CO2 and Temperature Transmitters.

The Telaire Ventostat 8000 Series represents a full range of wall mount CO2, humidity and temperature transmitters with display options plus active humidity and temperature outputs. Provides controlled ventilation such as conference rooms, classrooms, meeting halls, etc. Easy installation and a clean, modern look. CO2 sensors are recommended as part of the COVID-19 response and ventilation (AIRAH).

  • Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low cost package
  • Patented ABC Logic™ self-calibration system eliminates the need for manual calibration in most applications
  • Lifetime CO2 calibration guarantee when using ABC Logic™
  • Mounting plate with two-piece terminal blocks provide quick, easy wiring
  • Gas permeable, water resistant CO2 diffusion filter prevents particulate and water contamination of the sensor
  • Locking screw secures cover and sensor to the mounting bracket for tamper resistance
  • Sensors are shipped factory calibrated
  • Modern enclosure
  • Conformal coating on 0-5000 ppm models
  • Low cost
  • Reliable (20 years of low-cost infrared sensor manufacturing)
  • Available CO2 and Temperature output options: Voltage 0-10V or 0-5V (switch selectable) Or current 4-20 mA, Relay
  • UIP software compatible for customizations
  • CE, RoHS, REACH and WEEE compliant
  • Lifetime calibration warranty
  • Relay output

Sensing Method: Non Dispersive Infrared (NDIR), gold plated optics, diffusion or flow through sampling (with Telaire’s Patented ABC Logic Self Calibrated Algorithm)

Measurement Range: 0 to 5000 ppm**

Dimensions: Overall 60 mm X 35 mm X 15 mm approx

Accuracy: 400-5000 ppm ± 75 ppm or 10% of reading, whichever is greater*

Terature Dependence: 0.2% FS per °C

Calibration Interval: Not Required

Response Time: 7 minutes (approx)

Signal Update: Every 4 seconds

Warm-Up Time: < 2 minutes (operational). 10 minutes (maximum accuracy)

Operating Conditions: 32°F to 122°F (0°C to 50°C). 0 to 95% RH, non-condensing

Storage Conditions: -40°F to 158°F (-40°C to 70°C)

Output: I2C Digital, see T6700 Series Application Guide for detail

Protection: IP65

Power Supply Requirements: 4.5-5.5 VDC. Peak 200mA (155mA typical). Average 25mA (20mA typical)

Warranty Terms: 12 months

Compliance: REACH, ROSH and Prop65 compliance. Flammability rating of enclosure UL94 5VA


* Tolerance based on span gas of ±2%
** Subjecting sensors to environments less than 400ppm for more than 15 minutes may affectaccuracy due to ABC Logic™ algorithm.