T5100 Series Wall Mount CO2 Transmitters

Model:

T5100

Brand

Telaire T5100 Series of Wall Mount CO2 Transmitters offers low cost, high performance CO2 transmitters for the building controls market. It works seamlessly with building automation systems, and allows you to simply and effectively control fresh air. Demand-controlled ventilation using CO2 sensors prevents energy loss from over-ventilation while maintaining indoor air quality.

  • Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low cost package
  • Patented ABC Logic™ self-calibration system eliminates the need for manual calibration in most applications
  • Lifetime CO2 calibration guarantee when using ABC Logic™
  • Mounting plate with two-piece terminal blocks provide quick, easy wiring
  • Gas permeable, water resistant CO2 diffusion filter prevents particulate and water contamination of the sensor
  • Locking screw secures cover and sensor to the mounting bracket for tamper resistance
  • Sensors are shipped factory calibrated
  • Modern enclosure
  • Low cost
  • Reliable (20 years of low-cost infrared sensor manufacturing)
  • UIP software compatible for customizations
  • CE, RoHS, REACH and WEEE compliant
  • Lifetime calibration warranty
  • Two enclosure sizes for regional acceptance

Sensing Method: Non-dispersive infrared (NDIR) absorption. Gold-plated optics. Patented ABC Logic self calibration algorithm

CO2 Measurement Range: 0 to 2000 ppm. (0 ppm = 0 V, 4 mA)

CO2 Accuracy: ±30 ppm or 3% of the reading shown, whichever is higher *

Power Supply Requirements: 18-30 VAC RMS, 50/60 Hz, or 18 to 42 VDC, polarity protected*AHRAE — regulation 62 states maximum indoor CO2 level of 1000 ppm

Power Consumption: Typical 0.7 W at nominal voltage of 24V AC RMS

Terature Dependence: 0.2% FS per °C (±0.11% per °F)

Stability: <2% of FS over life of sensor (15 years)

Pressure Dependence: 0.135% of reading per mm Hg

Certifications: CE EMC, RoHS, REACH and WEEE compliant

Signal Update: Every 5 seconds

CO2 Warm-Up Time: <2 minutes (operational). 10 minutes (maximum accuracy)

Operating Conditions: 32°F to 122°F (0°C to 50°C). 0 to 95% RH, non-condensing

Storage Conditions: -40°F to 158°F (-40°C to 70°C)

Flammability Classification: UL94 5VA

Output: Field selectable voltage or current. Field selectable voltage or current. Voltage only (0-10 or 0-5V)- Current only (4-20 mA)

Analog (CO2): 0 to 5 V, or 0 to 10 V jumper selectable (100 Ω output impedance). Or 4 to 20 mA (RL maximum 500 Ω). Voltage and current outputs are not available simultaneously. Digital to analog error ±1%